Home > Products > Industrial Battery > Industrial OPzV Battery > Storage power Telecom station OPzV Charger battery 2V

Storage power Telecom station OPzV Charger battery 2V

Payment Type:
L/C,T/T,D/P
Incoterm:
FOB,CFR,CIF
Min. Order:
100 Piece/Pieces
Transportation:
Ocean,Land
Share:
  • Product Description
Overview
Product Attributes

Model No.CFPV2600

Brandfirstpower

TypeLead-Acid Batteries

UsageUPS

Nominal Voltage2V

Discharge RateMedium Discharge Rate

ShapeSquare Battery

ElectrolyteAcid

InstallationFixed

RechargeableChargeable

High Rate Discharge BatterySealed Lead Acid Battery

Deep Cycle Battery FactoryBack-up Battery

UPS Battery FactorySolar Power Battery

OPzV BatteryTelecommunication Battery

Supply Ability & Additional Information

Packaging Carton & pallet packaging

Productivity2000, 000kvah/ Year

TransportationOcean,Land

Place of Originchina

Supply Ability2000, 000kvah/ Year

Certificateiso,UL,CE

Payment TypeL/C,T/T,D/P

IncotermFOB,CFR,CIF

Packaging & Delivery
Selling Units:
Piece/Pieces
Package Type:
Carton & pallet packaging

Storage Power Opzv Battery CFPV2600,capacity :2V600Ah batteries  is Sealed Lead Acid Battery. Never charge the battery in a sealed container.
Never disassemble the battery.
Never short-circuit battery terminals.
Never incinerate batteries, for they may explode.
Do not press and/or bend the terminals, or overheat
them.
can be used for just about every application, including: UPS Backup Systems, Alarm Systems, Fire Alarm Systems, Medical Equipment, Test Equipment, and much more. 


 Electrical Electronics


Specifications

Nominal Voltage

2 V

Capacity

(25)

10HR(1.80V)

600 Ah

3HR(1.75V)

468Ah

1HR(1.75V)

322Ah

Dimension

Length

206±2mm (8.11inch)

Width

145±1mm (5.71inch)

Height

646±3mm (25.43inch)

Total Height

681±3mm (26.81inch)

Approx. Weight

42.3kg (93.2lbs)±5%

Terminal type

T10

Internal resistance

(Fully charged, 25)

Approx. 0.45mΩ

Capacity affected by temperature (10HR)

40

102%

25

100%

0

85%

-15

65%

Self-discharge

(25)

3 month

Remaining Capacity: 93%

6 month

Remaining Capacity: 85%

12 month

Remaining Capacity: 72%

Nominal operating temperature

25±3(77℉±5)

Operating temperature range

Discharge

-15~50(5℉~122)

Charge

-10~50(14℉~122)

Storage

-20~50(-4℉~122)

Float charging voltage(25)

2.25 to 2.30V

Temperature compensation:

-3mV/

Cyclic charging voltage(25)

2.30 to 2.35V

Temperature compensation:

-5mV/

Maximum charging current

120A

Terminal material

Copper

Maximum discharge current

2400A(5 sec.)

Designed floating life(20)

20 years

Gelled electrolyte technology;

Tubular Positive Plate;

◆ ABS container.






 

Constant Current Discharge Characteristics (A, 25)

F.V/TIME

30min

60min

2h

3h

4h

5h

6h

8h

10h

20h

24h

48h

72h

100h

120h

1.60V

510

342

207

159

129

110

94.2

74.1

61.1

32.4

27.9

14.8

10.1

7.41

6.30

1.65V

500

337

206

158

128

109

93.7

73.6

61.0

32.3

27.8

14.8

10.1

7.38

6.29

1.70V

485

328

204

157

127

108

93.0

73.1

60.8

32.2

27.6

14.7

10.0

7.35

6.26

1.75V

473

322

201

156

126

107

92.4

72.6

60.4

32.0

27.6

14.6

9.97

7.31

6.22

1.80V

455

312

196

151

122

104

89.6

70.4

60.0

31.8

27.5

14.5

9.90

7.26

6.18

Constant Power Discharge Characteristics (Watt, 25)

F.V/TIME

30min

60min

2h

3h

4h

5h

6h

8h

10h

20h

24h

48h

72h

100h

120h

1.60V

954

650

400

312

252

216

186

147

122

64.7

56.1

29.9

20.6

15.2

12.9

1.65V

935

640

397

310

250

215

185

146

121

64.6

56.0

29.8

20.5

15.1

12.9

1.70V

906

624

394

308

249

213

183

145

121

64.4

55.6

29.7

20.5

15.1

12.8

1.75V

884

611

388

306

247

212

182

144

120

64.0

55.5

29.5

20.3

15.0

12.8

1.80V

852

593

378

297

240

205

177

139

119

63.6

55.2

29.3

20.2

14.9

12.7

Note: The above characteristics data can be obtained within three charge/discharge cycles.







International certifications:
ISO9001 approval, FN: Q3105105131
ISO14001 CTC04912E10302ROM
OHS MS18001 04912S10150ROM
UL approval, FN:MH28204
CE approval, FN:G2M20201-0102-E-16
KS approval, FN:KS C 8519
VDS approval

BS approval


FP Series Battery General Features

  • Nonspillable
  • Sealed and Maintenance-free Operation
  • High Quality and High Reliability
  • Exceptional Deep Discharge Recovery
  • Low Self-discharge
  • Long Service Life
  • Solid Copper Terminals
  • Tank-formed Plates
  • Computer-aided Design and Manufacturing
  • UL, CE, VdS Approved

Typical Applications

  • Telecommunication equipment
  • Electronic instruments
  • Fire alarm
  • Security devices
  • UPS power supply
  • Emergency lighting









Product Categories : Industrial Battery > Industrial OPzV Battery

Home > Products > Industrial Battery > Industrial OPzV Battery > Storage power Telecom station OPzV Charger battery 2V
Email to this supplier
  • *Subject:
  • *To:
    Ms. SALES
  • *Email:
  • *Message:
    Your message must be between 20-8000 characters
Send Inquiry
*
*

Related Products List

Home

Product

Whatsapp

About Us

Inquiry

We will contact you immediately

Fill in more information so that we can get in touch with you faster

Privacy statement: Your privacy is very important to Us. Our company promises not to disclose your personal information to any external company with out your explicit permission.

Send