Contact Supplier

Ms. SALES
Leave a messagePayment Type: | L/C,T/T,D/P |
---|---|
Incoterm: | FOB,CFR,CIF |
Min. Order: | 100 Piece/Pieces |
Delivery Time: | 30 Days |
Basic Info
Model No.: LFP12180D
Type: Lead-Acid Batteries
Usage: UPS
Nominal Voltage: 12V
Discharge Rate: Medium Discharge Rate
Shape: Square Battery
Electrolyte: Acid
Installation: Fixed
Rechargeable: Chargeable
High Rate Discharge Battery: Sealed Lead Acid Battery
Deep Cycle Battery Factory: Back-up Battery
UPS Battery Factory: Solar Power Battery
Additional Info
Packaging: Carton & pallet packaging
Productivity: 2000, 000kvah/ Year
Brand: firstpower
Transportation: Ocean,Land
Place of Origin: china
Supply Ability: 2000, 000kvah/ Year
Certificate: iso,UL,CE
Product Description
Reserve Deep Cycle Battery LFP12180D,capacity :12V180Ah batteries is Sealed Lead Acid Battery. can be used for ForkLifts UninterruptiblePowerSupplies EmergencyLighting Wheelchairs TelecomBack-UpPowerSupplies
LawnandGardenTools EngineStarters
Specifications
Nominal Voltage | 12 V | ||
Capacity (25℃) | 10HR(10.8V) | 180 Ah | |
5HR(10.5V) | 157.5Ah | ||
1HR(9.60V) | 113Ah | ||
Dimension | Length | 494±2mm (19.45inch) | |
Width | 206±2mm (8.11inch) | ||
Height | 209±2mm (8.23inch) | ||
Total Height | T20: 235±2mm (9.25inch) | ||
T11: 212±2mm (8.35inch) | |||
Approx. Weight | 54kg (119.1lbs)±4% | ||
Terminal type | T20/T11 | ||
Internal resistance (Fully charged, 25℃) | Approx. 3.3mΩ | ||
Capacity affected by temperature (10HR) | 40℃ | 102% | |
25℃ | 100% | ||
0℃ | 85% | ||
-15℃ | 65% | ||
Self-discharge (25℃) | 3 month | Remaining Capacity: 91% | |
6 month | Remaining Capacity: 82% | ||
12 month | Remaining Capacity: 65% | ||
Nominal operating temperature | 25℃±3℃(77℉±5℉) | ||
Operating temperature range | Discharge | -15℃~50℃(5℉~122℉) | |
Charge | -10℃~50℃(14℉~122℉) | ||
Storage | -20℃~50℃(-4℉~122℉) | ||
Float charging voltage(25℃) | 13.50 to 13.80V Temperature compensation: -18mV/℃ | ||
Cyclic charging voltage(25℃) | 14.50 to 14.90V Temperature compensation: -30mV/℃ | ||
Maximum charging current | 54A | ||
Terminal material | T20: Lead, T11: Copper | ||
Maximum discharge current | 1400A(5 sec.) | ||
Designed floating life(20℃) | 12~15 years | ||
◆ Absorbent glass mat technology;
◆ Recognized by UL & CE;
◆ ABS container.
Constant Current Discharge Characteristics (A, 25℃)
F.V/TIME | 15min | 30min | 60min | 2h | 3h | 4h | 5h | 6h | 8h | 10h | 20h |
9.60V | 300 | 182 | 113 | 65.8 | 45.9 | 37.6 | 32.1 | 28.1 | 22.0 | 18.3 | 9.62 |
9.90V | 293 | 178 | 111 | 65.4 | 45.6 | 37.4 | 31.9 | 27.9 | 21.9 | 18.3 | 9.60 |
10.2V | 282 | 173 | 108 | 64.8 | 45.3 | 37.2 | 31.7 | 27.7 | 21.8 | 18.2 | 9.57 |
10.5V | 272 | 169 | 106 | 63.8 | 45.0 | 36.9 | 31.5 | 27.5 | 21.6 | 18.1 | 9.52 |
10.8V | 258 | 162 | 103 | 62.2 | 43.7 | 35.8 | 30.6 | 26.7 | 21.0 | 18.0 | 9.45 |
Constant Power Discharge Characteristics (Watt, 25℃)
F.V/TIME | 15min | 30min | 60min | 2h | 3h | 4h | 5h | 6h | 8h | 10h | 20h |
9.60V | 3294 | 2040 | 1285 | 762 | 540 | 443 | 380 | 332 | 262 | 219 | 115 |
9.90V | 3215 | 1999 | 1266 | 757 | 537 | 440 | 378 | 330 | 260 | 218 | 115 |
10.2V | 3096 | 1938 | 1234 | 750 | 533 | 437 | 375 | 328 | 258 | 218 | 115 |
10.5V | 2991 | 1891 | 1209 | 739 | 529 | 434 | 372 | 326 | 257 | 216 | 114 |
10.8V | 2833 | 1822 | 1172 | 720 | 513 | 421 | 361 | 316 | 249 | 215 | 113 |
Note: The above characteristics data can be obtained within three charge/discharge cycles.
BS approval
FP Series Battery General Features
Typical Applications
Product Categories : Network Power/Reserve Battery > Reserve Deep Cycle Battery