Home > Products > Network Power/Reserve Battery > High Rate Discharge Battery > Best Nimh Rechargeable Batteries

Best Nimh Rechargeable Batteries

Payment Type:
L/C,T/T,D/P
Incoterm:
FOB,CFR,CIF
Min. Order:
100 Piece/Pieces
Transportation:
Ocean,Land
Share:
  • Product Description
Overview
Product Attributes

Model No.LFP1265HR

Brandfirstpower

TypeLead-Acid Batteries

UsageUPS

Nominal Voltage12V

Discharge RateHigh Discharge Rate

ShapeSquare Battery

ElectrolyteAcid

InstallationFixed

RechargeableChargeable

High Rate Discharge BatterySealed Lead Acid Battery

UPS Battery FactorySolar Power Battery

Back Up Battery FactoryBack-up Battery

Supply Ability & Additional Information

Packaging Carton & pallet packaging

Productivity2000, 000kvah/ Year

TransportationOcean,Land

Place of Originchina

Supply Ability2000, 000kvah/ Year

Certificateiso,UL,CE

Payment TypeL/C,T/T,D/P

IncotermFOB,CFR,CIF

Packaging & Delivery
Selling Units:
Piece/Pieces
Package Type:
Carton & pallet packaging

 LFP1265HR is a typical High Rate Discharge Battery special designed for all kinds of high-power-ouput using application, 

It is a non-spillable and sealed and Maintenance-free operation battery, with high quality and high reliability, good deep discharge recovery, low self-discharge ,etc. The battery apply solid copper terminals,tank-formed plates computer-aided design and manufacturing

Main features as follow:
*
 Standby use.  

*  High rate discharge construction.

* ISO9001, 14001, OHSMS 18001 certified.

  UL, CE, VdS Approved. UL recognized components under UL 1989 (file number MH28204 ).

*With isolated seal, it can be put in horizontal way, vertical way and side way, its safety and functions totally will not be affected.

* With special formula to manufacture lead calcium alloy as well as automatic progresses, gassing will be less.
* Long life, low self-discharge rate and high reliability.
* It has safety, low resistance so recharge is easy and energy output is more remarkable.
* Container material could be frame retardant ABS or PP with ranking UL 94V-0 by model.
When it is used in safe surroundings, the battery is maintenance free, adding water is unnecessary and it can be recharged repeatedly.
*  Batteries are strictly tested by computer charge/discharge system.
*  Complies with IATA/ICAO Special Provision A67 for air transport.
*  Classified per MG Amendment 27 as a non-hazardous material for water transport.
* Recognized by DOT as "Dry charge" 49 CFR 171-189 for surface transport.






Specifications

Nominal Voltage

12 V

Number of cell

6 cells

Capacity(10HR, 25)

65 Ah

Capacity(15min.rate, 25)

240 Watts/cell

Dimension

Length

350±2mm (13.78inch)

Width

167±2mm (6.57inch)

Height

179±2mm (7.05inch)

Total Height

T5: 186±2mm (7.32inch)

T9: 179±2mm (7.05inch)

Approx. Weight

21.5kg (47.4lbs)±5%

Terminal type

T5/T9

Internal resistance

(Fully charged, 25)

Approx. 5.5mΩ

Capacity affected by temperature (20HR)

40

102%

25

100%

0

85%

-15

65%

Self-discharge

(25)

3 month

Remaining Capacity: 91%

6 month

Remaining Capacity: 82%

12 month

Remaining Capacity: 65%

Nominal operating temperature

25±3(77℉±5℉)

Operating temperature range

Discharge

-15~50(5℉~122)

Charge

-10~50(14℉~122)

Storage

-20~50(-4℉~122)

Float charging voltage(25)

13.50 to 13.80V

Temperature compensation:

-18mV/

Cyclic charging voltage(25)

14.50 to 14.90V

Temperature compensation:

-30mV/

Maximum charging current

19.5A

Terminal material

Copper

Maximum discharge current

650A(5 sec.)

Designed floating life(20)

7~10 years

◆ Absorbent glass mat technology;

◆ Recognized by UL & CE;

◆ ABS container.







 

Constant Current Discharge Characteristics (A, 25)

F.V/TIME

5min

10min

15min

20min

30min

45min

60min

2h

3h

5h

10h

20h

1.60V/cell

235

157

128

102

72.6

54.1

44.1

23.8

17.0

11.9

6.68

3.54

1.65V/cell

228

152

125

100

71.1

53.0

43.5

23.6

16.9

11.9

6.67

3.53

1.67V/cell

224

149

124

98.4

70.3

52.4

43.0

23.5

16.9

11.8

6.66

3.53

1.70V/cell

218

146

120

96.3

69.0

51.4

42.4

23.4

16.8

11.8

6.65

3.52

1.75V/cell

209

139

116

93.1

67.3

50.1

41.5

23.0

16.7

11.7

6.61

3.50

1.80V/cell

197

132

110

88.1

64.8

48.3

40.2

22.5

16.2

11.3

6.57

3.48

Constant Power Discharge Characteristics (Watt/cell, 25) 

F.V/TIME

5min

10min

15min

20min

30min

45min

60min

2h

3h

5h

10h

20h

1.60V/cell

427

294

247

198

140

104

85.2

46.3

33.6

23.6

13.4

7.08

1.65V/cell

415

286

241

193

137

102

83.9

46.0

33.4

23.5

13.3

7.07

1.67V/cell

408

281

240

190

136

101

83.0

45.9

33.3

23.4

13.3

7.06

1.70V/cell

398

274

232

186

133

99.2

81.8

45.6

33.1

23.3

13.3

7.05

1.75V/cell

380

262

225

180

130

96.8

80.1

44.9

32.9

23.2

13.2

7.00

1.80V/cell

359

247

213

170

125

93.2

77.7

43.8

31.9

22.5

13.1

6.96

Note: The above characteristics data can be obtained within three charge/discharge cycles.     








International certifications:
ISO9001 approval, FN: Q3105105131
ISO14001 CTC04912E10302ROM
OHS MS18001 04912S10150ROM
UL approval, FN:MH28204
CE approval, FN:G2M20201-0102-E-16
KS approval, FN:KS C 8519
VDS approval

BS approval


Typical Applications: 

Alarm System
Cable Television
Communication Equipment
Control Equipment
Security System
Medical Equipment
UPS
Power Tools
Toys
Emergency Power System 




Product Categories : Network Power/Reserve Battery > High Rate Discharge Battery

Email to this supplier
  • *Subject:
  • *To:
    Ms. SALES
  • *Email:
  • *Message:
    Your message must be between 20-8000 characters
Send Inquiry
*
*

Related Products List

Home

Product

Whatsapp

About Us

Inquiry

We will contact you immediately

Fill in more information so that we can get in touch with you faster

Privacy statement: Your privacy is very important to Us. Our company promises not to disclose your personal information to any external company with out your explicit permission.

Send